Permit: T02ME00688

Parcel: 123021980


Addresses:

1904 N TUCSON BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/11/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
02/05/2003 MECHANICAL - FINAL Denied 1.) #10 WIRE IS NOT ADEQUATE FOR 60 AMP. CIRCUIT FROM ELEC. DISCONNECT TO A/C UNIT. USE #6. WIRE.
2.) MARK UNIT DATA PLATE W/PROPER HEAT KIT INSTALLED & FUSE UNIT ACCORDINGLY. RECALL FOR INSPECTION.