Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*PATCH ON EXISTING RET. AIR ILL IS SEALED. | |
| 02/05/2003 | MECHANICAL - FINAL | Denied | 1. PATCH HOLE IN SIDE OF DUCT ON ROOF WITH SHEET METAL NOT TAPE. 2.) MARK DATA PLATE W/PROPER HEAT KIT INSTALLED & FUSE UNIT ACCORDINGLY. 3.) #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT FROM DISCONNECT TO A/C UNIT RECALL FOR INSPECTION. |