Permit: T02ME00672

Parcel: 13315058A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02ME00672

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
11/07/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) PAINT EXPOSED PVC W/LATEL PAINT.
2.) BLOCK & CLAMP CONDENSATE DRAIN. TERMIANTE INTO VENT STACK WITH A TEE NOT AN ELBOW.
3.) BLOCK & CLAMP GAS LINES
4.) PROVIDE AN OUTSIDE AIR VENT. MUST BE 10' AWAY FROM SEWER VENTS.
5.) PROVIDE A SUN SHIELD OVER CANVAS CONNECTOR.
6.) #8 WIRE IS NOT ADEQUATE FOR 60 AMPS CIRCUIT. RECALL FOR INSPECTION.