Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/29/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*TEST OK CALL GAS CO. |
| 10/23/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*GAS LINE HOLDING PRESSURE. MUST HAVE MIN 10 LB. TEST. SECURE GAS LINE TO WALL RECALL FOR FINAL. |
| 10/16/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
COND. DRAIN, ELIMINATE EXTERNAL TRAP. UNIT HAS BUILT IN TRAP. CANNOT TERMINATE CONDENSATE OUT OF ROOF SCUPPER. MUST CONTINUE DOWN TO SOIL THAT ABSORB IT PAINT PVC PIPING. 2.) COVER THERMOSTAT WERE EXPOSED TO SUN. 3.) ELECTRIC SWITCH. PROVIDE SLEEVE AT REAR OF BOX INTO UNIT CAN'T LEAVE SHARP ROW EDGE WILL CUT WIRE. 4.) THREE 3" & 1 1/2" WET SEWER VENTS ARE BLOCKED BY OVERHEAD 10" X 8" DUCT. RE ROUTE AS NECESSARY CORRECT/RECALL. |