Permit: T02ME00608

Parcel: 128040530

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/20/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*1.) #8 WIRE FROM ELEC. DISCONNECT TO CONDENSOR NOT ADEQUATE FOR 60 AMP. USE #6. WIRE OR CHANGE FUSES TO 50 AMP. RECALL FOR INSPECTION. 2.) ISOLATE COPPER LINE FROM CONTACTING STEEL STRAPS OUTSIDE AT CONDENSOR.
09/19/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*