Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/20/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) #8 WIRE FROM ELEC. DISCONNECT TO CONDENSOR NOT ADEQUATE FOR 60 AMP. USE #6. WIRE OR CHANGE FUSES TO 50 AMP. RECALL FOR INSPECTION. 2.) ISOLATE COPPER LINE FROM CONTACTING STEEL STRAPS OUTSIDE AT CONDENSOR. |
| 09/19/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |