Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00586
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. | |
| 08/29/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) CONDENSATE CAN NO LONGER TERMINATE INTO A WASTE VENT. 2.) MARK DATA PLATE W/PROPER HEAT KIT INSTALLED & FUSE UNIT ACCORDINGLY. 3.) TRAP ON CONDENSATE DRAIN NOT DEEP ENOUGH PROVIDE INSTALLATION INSTRUCTIONS OR BUILD DEPTH OF TRAP 1.5 TIMES THE EXTERNAL STATIC PRESSURE. RECALL FOR INSPECTION. |