Permit: T02ME00555

Parcel: 11006159B

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/27/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
08/21/2002 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*ELEC DISCONNECT & A/C UNIT NOT GROUNDED OR BONDED. DISCONNECT IS OVERFUSED MAX. IS 25 AMP. USE A CHASE NIPPLE OR BUSHING WHERE ELEC. WIRES ENTER THE A/C UNIT. RECALL FOR INSPECTIONS.