Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/27/2002 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/21/2002 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*ELEC DISCONNECT & A/C UNIT NOT GROUNDED OR BONDED. DISCONNECT IS OVERFUSED MAX. IS 25 AMP. USE A CHASE NIPPLE OR BUSHING WHERE ELEC. WIRES ENTER THE A/C UNIT. RECALL FOR INSPECTIONS. |