Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/29/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*MECHANICAL CORRECTIONS, OK. |
| 08/22/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) UNIT IMPROPERLY FUSED. 2.) DATA PLATE ON UNIT INCOMPLETE DOES UNIT HAVE AUX. HEAT YES? 3.) NEW 60 AMP SWITCH INSTALLED ON RETURN AIR DUCT. SWITCH IS BLOCKED BY REFRIG. LINES. FROM WALK IN CONDENSER. 4. ) IMPROPER FITTING USED ON LB AT OLD 60 AMP SWITCH. 5.) EMT 3/4" ON ROOF SURFACE. NEED TO ELEVATE, BLOCK, CLAMP AS NECESSARY. 6.) BLOCK, CLAMP CARFLEX INTO UNIT. |