Permit: T02ME00551

Parcel: 12501004B


Addresses:

2648 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/29/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*MECHANICAL CORRECTIONS, OK.
08/22/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) UNIT IMPROPERLY FUSED. 2.) DATA PLATE ON UNIT INCOMPLETE DOES UNIT HAVE AUX. HEAT YES? 3.) NEW 60 AMP SWITCH INSTALLED ON RETURN AIR DUCT. SWITCH IS BLOCKED BY REFRIG. LINES. FROM WALK IN CONDENSER. 4. ) IMPROPER FITTING USED ON LB AT OLD 60 AMP SWITCH. 5.) EMT 3/4" ON ROOF SURFACE. NEED TO ELEVATE, BLOCK, CLAMP AS NECESSARY. 6.) BLOCK, CLAMP CARFLEX INTO UNIT.