Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02ME00501

Parcel: 133090370


Addresses:

1615 N JENIFER AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/01/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
07/31/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*#8 WIRE FROM ELEC. DISCONNECT TO CONDENSOR NOT ADEQUATE SIZE FOR 60 AMP CIRCUIT SEE TABLE 310-16 1999 NEC.