Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00492
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 07/31/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*#8 WIRE FROM ELEC. DISCONNECT TO CONDENSOR NOT ADEQUATE FOR 60 AMP CIRCUIT SEE TABLE 310-16-1999 NEC. CORRECT & RECALL FOR FINAL. |