Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/28/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*A ROOF JACK IS REQUIRED WHERE ELEC. CONDUIT PENETRATES THE ROOF. 2.) RECALL FOR INSPECTION. |
| 06/25/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES ROOF. 2.) #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT TO ELEC. DISCONNECT. RECALL FOR INSPECTION. |