Permit: T02ME00369

Parcel: 133181510


Addresses:

6911 E 4TH ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/28/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*A ROOF JACK IS REQUIRED WHERE ELEC. CONDUIT PENETRATES THE ROOF. 2.) RECALL FOR INSPECTION.