Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/20/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE. |
| 06/14/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MARK THE UNIT DATA PLATE W/ THE PROPER HEAT KIT INSTALLED & FUSSE UNIT ACCORDINGLY IF MORE THEN MARK IT AS SUCH. 2.) PROVIDE A ROOF JACK WHERE ELEC CONDUIT PENETRATES THE ROOF. 3.) CONDENSATE CANNOT TERMINATE INTO A WASTE E VENT SMALLER THAN 2" USE A TEE IF TERMINATING OVER THE TOP. IT WOULD BE BETTER TO DISCHARGE THE WATER TO THE GROUND INSTEAD OF CROSS CONNECTING YOUR AC UNITS WITH THE SEWER. 4.) PAINT EXPOSED PVC & FITTINGS W/LATEX PAINT. BLOCK & CLAMP PVC MAX 4' INTERVALS. RECALL FOR INSPECTION. |