Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1.) CONDENSATE DRAIN NEEDS TO BE TRAPED. 2.) MAX FUSE SIZE 45AMPS UNIT FUSED AT 50AMPS. 48,000 BTUH COOL 90M HEAT. |