Permit: T02ME00240

Parcel: 136343690


Addresses:

7470 E 45TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/21/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000* ALL CORRECTION HAVE BEEN MADE.
04/29/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) 3/8" I.D. X 3' GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 90,000 BTU. SEE LISTING ON FLEX CONNECTOR. 2.) PAINT EXPOSED PVC W/LATEX PAINT. 3.) CONDENSATE CANNOT DRIP OVER THE EDGE OF THE ROOF. PIPE MUST GO TO WITHIN 6" OF THE GROUND. BLOCK & CLAMP PVC MIN. 4' INTERVALS CORRECT & RECALL FOR INSPECTION.