Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2002 |
MECHANICAL - FINAL |
|
Approved |
|
| 06/18/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*STRAP FLEX DUCT 2/ 1 1/2" WIDE STRAP. PANDUIT STRAPS ARE NOT APPROVED HANGERS. ATTACH STRAPS TO THE STRUCTURE, NOT THE INSULATION PAPER ON THE HOME. RECALL FOR INSPECTION. |
| 05/20/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) STRAP ALL FLEX DUCT UP OFF OF DIRT. DUCTS SHALL NOT BE INSTALLED IN OR WITHIN 4" OF THE EARTH. SECTION 603.12 2000 IMC. 2.) PAINT FITTINGS ON EXPOSED PVC. RECALL FOR FINAL INSPECTION. 3.) SEAL THE OPENING WHERE LOW VOLTAGE CONDUIT EXITS FROM UNDER HOME. |