Permit: T02ME00220

Parcel: 10706014G

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02ME00220

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE.
07/29/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE THE LISTING FOR THE WIRE USED TO POWER THE ELEC. DISCONNECT. I SEE NO LISTING. 2.) ROMEX CONNECTOR ON CIRCUIT BREAKERS PANEL NOT CLAMPED OVER WIRE. 3.) USE A CHASE NIPPLE WHERE WIRES PENETRATE CABINET OF CONDENSOR. 4.) PROVIDE A HOSE CLAMP WHERE PVC CONNECTS TO RUBBER HOSE ON CONDENSATE DRAIN. RECALL FOR INSPECTION.