Permit: T02ME00207

Parcel: 12108042C


Addresses:

6152 E FAIRMOUNT ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/03/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*CORRECTION HAVE BEEN MADE.
05/29/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999* 1.) AIR HANDLER NOT FUSED PROPERLY AT 40 AMP. 30 AMP IS MAX. FUSE SIZE. 2.) VENT ON CONDENSATE DRAIN LINE MUST BE DOWNSTREAM OF TRAP. RECALL FOR INSPECTION.