Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02ME00197

Parcel: 113090980


Addresses:

2620 N TYNDALL AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/23/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
05/13/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
05/10/2002 MECHANICAL - FINAL Partial Approval
04/12/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE TRAP ON CONDENSATE DRAIN. 2. PROVIDE A FUSE STAT FOR ELECTRICAL PLUG. 3.) LOW COMBUSTION AIR VENT MUST BE WITHIN 12" OF FLOOR. WHERE IS THE HIGH COMBUSTION VENT? 4.) PROVIDE A FILTER IN THE BOTTOM OF FURNACE. 5.) RETURN DUCT CUT IN THE BACK SIDE OF FURNACE TERMINATING IN ATTIC & ABOVE FITER COMPARTMENT. 6.) RETURN PLENUM HAS EXPOSED DIRT INSIDE 7.) INSULATE SUPPLY DUCT IN DROP CEILING. 8.) PROVIDE A HOSE CLAMP ON CONDENSATE PUMP. 9.) ELECTRICAL CIRCUIT PANEL DOES NOT HAVE ADEQUATE CLEARANCE FOR SERVICE. 10.) YOU CANNOT TERMINATE DOUBLE WALL PIPE INTO SINGLE WALLL. 11.) VINYL HOSE NOT APPROVED FOR OUTDOOR USE. MUST DRAIN WITHIN 6" OF THE GROND 12.) CONDENSOR OVERFUSED & DISCONNECT NOT WIRED CORRECTLY. 13.) GLUE SEAMS & JOINTS ON ARMA FLEX INSULATION. 14.) SEAL HOLE IN LAVE