Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00180
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE THE REQUIRED EXHAUST SYSTEM AND ALL SENSORS TO SHUT OFF GAS VALVES IN CASE OF A REFRIGERANT LEAK. PROVIDE AN ENGINEERED DRAWING APPROVED BY THE CITY OF TUCSON COMPLYING WITH SECTION 1105 2003 IMC |
|
| 06/05/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*PROVIDE SENSORS TO SHEET DOWN EQUIPMENT IN CASE OF REFRIGRANT LEAK. PROVIDE AN EXHAUST SYSTEM TO REMOVE ANY REFRIGERANT FUNES. RECALL FOR INSPECTION. |