Permit: T02ME00131

Parcel: 136042760

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/26/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE.
03/20/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*
03/12/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999* 1.) PROVIDE A TRAP ON CONDENSATE DRAIN AS PER MANUFACTURES SPECS. 2.) #8 WIRE FROM DISCONNECT TO CONDENSOR NOT ADEQUATE SIZE FOR 60 AMP. 3.) STAT WIRE TO CONDENSOR NOT APPROVED FOR OUTDOOR USE. 4.) OBTAIN A PERMIT FOR THE NEW WATER HEATER & CALL FOR INSPECTION.