Permit: T02ME00125

Parcel: 116151620

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/11/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*PROVIDE OUTSIDE AIR VENTS ON AC UNITS 2.) REMOVE UNION FROM GAS LINE ON ROOF & USE REVERSE THREAD COUPLINGS & NIPPLES 3.) PROVIDE A PRESSURE TEST ON GAS SYSTEM TO NEW FURNACES. 4.) GAS PIPE TOUNITS ON ROOF NOT ADEQUATE SIZE. PROVIDE CALCULATIONS FOR SIZING YOUR GAS PIPE 5.) SUPPORT PIPE IN ATTIC.