Permit: T02ME00121

Parcel: 116020290

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02ME00121

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
04/03/2002 MECHANICAL - FINAL Partial Approval 1. CONDENSATE DRAIN, PVC NEEDS TO BE PAINTED. 2.) STABILEIZE ELECT SWITCH. IT'S LOOSE ON EMT. 3.) DATA PLATE FOR AUX. HEAT STRIP IS NOT MARKED. MARK DATA PLATE AND LEAVE PROPERLY FUSED. 4.) PLOT FORM EXISTING IS BLOCKING REAR ACCESS PANEL ON NEW UNIT. THIS IS PROBABLY BLOWER COMPARTMENT. CHECK UP RIGHTS SO SERVICE ACCESS IS NOT BLOCKED.