Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/20/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. |
| 03/14/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) YOU CANNOT TERMINATE CONDENSATE INTO A WASTE VENT WITHOUT A FITTING. REPLACE THE TEE THAT YOU DAMAGED & FIND ANOTHER VENT TO TERMINATE INTO. FIRST SECTION OF DRAIN RUNS UPHILL. 2.) PROVIDE AN OUTSIDE AIR VENT 3. CANVAS CONNECTORS NOT COMPLETELY COVERED FROM SUN LIGHT. 4.) MARK DATA PLATE W/PROPER HEAT KIT & FUSE UNIT ACCORDINGLY. |