Permit: T02ME00116

Parcel: 13409018C


Addresses:

8654 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02ME00116

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE.
03/14/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) YOU CANNOT TERMINATE CONDENSATE INTO A WASTE VENT WITHOUT A FITTING. REPLACE THE TEE THAT YOU DAMAGED & FIND ANOTHER VENT TO TERMINATE INTO. FIRST SECTION OF DRAIN RUNS UPHILL. 2.) PROVIDE AN OUTSIDE AIR VENT 3. CANVAS CONNECTORS NOT COMPLETELY COVERED FROM SUN LIGHT. 4.) MARK DATA PLATE W/PROPER HEAT KIT & FUSE UNIT ACCORDINGLY.