Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00116
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. | |
03/14/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) YOU CANNOT TERMINATE CONDENSATE INTO A WASTE VENT WITHOUT A FITTING. REPLACE THE TEE THAT YOU DAMAGED & FIND ANOTHER VENT TO TERMINATE INTO. FIRST SECTION OF DRAIN RUNS UPHILL. 2.) PROVIDE AN OUTSIDE AIR VENT 3. CANVAS CONNECTORS NOT COMPLETELY COVERED FROM SUN LIGHT. 4.) MARK DATA PLATE W/PROPER HEAT KIT & FUSE UNIT ACCORDINGLY. |