Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00115
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE. | |
03/14/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* MECH. FINISH. 1.) ACCESS TO BLOWER COMPARTMENT IS BLOCKED BY AN EVAP COOLER. SEE MANUFACTURERS INSTRUCTIONS FOR PROPER CLEARANCE. 2.) SEAL HOLES IN DISCONNECTS 3.) SM. UNIT PROVIDE AN OUTSIDE AIR VENT 4.) SM. UNIT IS OVER FUSED 5.) BLOCK & CLAMP GAS PIPE TO SMALL UNIT RECALL FOR INSPECTION. |