Permit: T02ME00082

Parcel: 114471460


Addresses:

2870 N ESSEL DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/28/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE.
03/21/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999* 1.) 60 FUSES TOO LARGE FOR #8 WIRE.USE #6 WIRE OR CHANGE FUSES. 2.) EXPOSED CONTROL WIRING MUST BE SUN RESISTANT RECALL FOR INSPECTION. RESISTANT. RECALL FOR INSPECTION.
03/11/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0920*PLEASE HAVE YOU CONTRACTOR CALL FOR AIR INSPECTION WHEN SOMEONE WILL BE HOME.