Permit: T02ME00073

Parcel: 136311980


Addresses:

3976 S HEADWIND DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/31/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE.
04/02/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) CIRCUIT OVERSIGNED MAX 35 AMP. 2.) SECONDARY DRAIN CANNOT TERMINATE INTO PRIMARY DRAIN. RUN TO CONSPICUOUS LOCATION. USE SECONDARY OUTLET ON FAN COIL TO DRAIN OVERFLOW. BE SURE TO USE A TRAP. 3.) FAN COIL NEEDS SEPERATE POWER FOR HEAT STRIP & FAN MOTOR OR PROVIDE ACCESSORY KIT. RECALL FOR INSPECTION.