Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/31/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. |
| 04/02/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CIRCUIT OVERSIGNED MAX 35 AMP. 2.) SECONDARY DRAIN CANNOT TERMINATE INTO PRIMARY DRAIN. RUN TO CONSPICUOUS LOCATION. USE SECONDARY OUTLET ON FAN COIL TO DRAIN OVERFLOW. BE SURE TO USE A TRAP. 3.) FAN COIL NEEDS SEPERATE POWER FOR HEAT STRIP & FAN MOTOR OR PROVIDE ACCESSORY KIT. RECALL FOR INSPECTION. |