Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00054
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE. | |
02/06/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*OUTSIDE SECTION-SPLIT SYSTEM HT. PUMP 060,000 BTUH PROVIDE SUPPORT. FIRST BEND REFRIGERENT LINE TO PREVENT DAMAGE IF STEPED ON PERMENTLY MARK UNIT NUMBER. 2.) ELECTRIC SWITCH ON ROOF. 30,000 BTUH COMB 60M HEAT REDUCING WASHERE BOTTOM OF SWITCH TOTALLY BROKEN PROVIDE LARGER REDING WASHERS LEAVE PROPERLY SUPPORTED. CONDENSATE DRAIN, CANT DUMP ONTO HARD SURFACE. SIDEWALLS PAVED PARKING ETC.TERMINATE INTO ADJOINING 3" ABS VENT, AS 3/4" PVC. TEE CHECK CIRCUIT BKR. PANEL PERMANENTLY LABEL PANEL NUMBER ON ROOF TOP SWITCH MAX FUSE SIZE, 35 AMPS. |