Permit: T02ME00054

Parcel: 115043330


Addresses:

1145 N 4TH AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02ME00054

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE.
02/06/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*OUTSIDE SECTION-SPLIT SYSTEM HT. PUMP 060,000 BTUH PROVIDE SUPPORT. FIRST BEND REFRIGERENT LINE TO PREVENT DAMAGE IF STEPED ON PERMENTLY MARK UNIT NUMBER. 2.) ELECTRIC SWITCH ON ROOF. 30,000 BTUH COMB 60M HEAT REDUCING WASHERE BOTTOM OF SWITCH TOTALLY BROKEN PROVIDE LARGER REDING WASHERS LEAVE PROPERLY SUPPORTED. CONDENSATE DRAIN, CANT DUMP ONTO HARD SURFACE. SIDEWALLS PAVED PARKING ETC.TERMINATE INTO ADJOINING 3" ABS VENT, AS 3/4" PVC. TEE CHECK CIRCUIT BKR. PANEL PERMANENTLY LABEL PANEL NUMBER ON ROOF TOP SWITCH MAX FUSE SIZE, 35 AMPS.