Permit: T02EL02504

Parcel: 104071150

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL02504

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/31/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) PLEASE SECURE GROUNDED ELECTRODE CONDUCTOR ACROSS CEMENT
2.) PLEASE VERIFY LISTING FOR GROUND CLAMPS. CAN NOT LOCATE ON CLAMP.
3.) SERVICE COVER TO BE ABLE TO OPEN 90
4.) ALL STRANDS OF CONDUCTOR TO BE UNDER TERMANAL AT BREAKER AND NEUTRAL BAR.
5.) FINISH TERMANATING ALL CONDUCTOR
6.) INSTALL CONDUCTOR AS PER MANUFACTURES INSTRUCTIONS FOR STIPPING DEPTH.