Permit: T02EL02500

Parcel: 138072230


Addresses:

942 W MILTON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/07/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 5/8/03 AT 9:15AM OK TO CLEAR/OK CABLE DROP.
05/02/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) ISOLATE NEUTRAL AND GROUND BAR A STURCTURE SUB PANEL IN BACK OF MAIN HOUSE.
2.) LABEL CIRCUIT BREAKERS AT NEW SUB PANEL.
3.) 2ND STRUCTURE IN BACK MUST HAVE ITS OWN GROUNDING ELECTRODE SYSTEM.
SEE ART 250 NEC TWO OR MORE STRUCTURES FED FROM COMMON SERVICE."
4.) CHASE NIPPLE NOT ALLOWED UNLESS A LOCKNUT INSTALLED TO BITE INTO METAL ENCLOSURE, TO ENSURE CONTINUITY OF METAL PARTS. USE SEALING LOCKNUT.
5.) BOND WATER & GAS 2ND STRUCTURE (VERIFY).