Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 5/8/03 AT 9:15AM OK TO CLEAR/OK CABLE DROP. | |
| 05/02/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1.) ISOLATE NEUTRAL AND GROUND BAR A STURCTURE SUB PANEL IN BACK OF MAIN HOUSE. 2.) LABEL CIRCUIT BREAKERS AT NEW SUB PANEL. 3.) 2ND STRUCTURE IN BACK MUST HAVE ITS OWN GROUNDING ELECTRODE SYSTEM. SEE ART 250 NEC TWO OR MORE STRUCTURES FED FROM COMMON SERVICE." 4.) CHASE NIPPLE NOT ALLOWED UNLESS A LOCKNUT INSTALLED TO BITE INTO METAL ENCLOSURE, TO ENSURE CONTINUITY OF METAL PARTS. USE SEALING LOCKNUT. 5.) BOND WATER & GAS 2ND STRUCTURE (VERIFY). |