Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
| 01/28/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) USE OF AN ANTI-OXID COMPOUND IS NEEDED FOR ALUMINIUM TERMANATIONS. 2.) PLEASE IDENTIFY THE GROUNDED CONDUCTOR AT TERMANATION. GROUND. 3.) NOTE: THIS SERVICE HAS 5 THROW OF THE HAND AT THIS TIME WITHOUT A MAIN. |
|
| 01/17/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 1/21/03 AT 9:15AM OK TO CLEAR PLEASE CALL AFTER CROSS OVER. | |
| 01/15/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) A PERMANENT METAL ADDRESS LABEL IS TO BE SCREWED OR RIVITED TO SERVICE. 2.) BONDING DEVICES ARE NEEDED ON BOTH SIDES OF NIPPLE AND RISER & 250-94. 3.) SUPPORT CONDUIT AND TIGHTEN FITTINGS AND BURY AS PER CODE DEPTHS 300-5. 4.) NEW BREAKERS TO BE LABELED. 5.) SERVICE TRENCH NOT TO BE LESS THAN 5' FROM INSIDE EDGE OF POOL/SPA 680-10. |