Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP CITY WILL NOTIFY TEP FOR CABLE DROP & POWER CLEARANCE BY 2: PM TODAY. | |
| 12/17/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) WIRE UNDERSIZED FOR 60 AMP FUSING AHEAD OF PUMP FEEDERS. PER 310-16NEC. 2.) COLOR CODE HI LEG ORANGE PER #9287 CITY ORDINANCE IF APPLICABLE. |