Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 12/30/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK 3/4' IMC CONDUIT INTRENCH 1.) CONDUITS UNDER ROADWAY TO BE AT 24" DEPTH PER 300.5 WE HAVE A SLEVE THAT INSTALLED WITHOUT INSPECTION AT 16" - 18" AT ISLAND OF ROADWAY. |
|
| 12/17/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) 3/4" PVC CONDUIT TO BE BURIED AS PER CODE 300-5. 2.) PLEASE VERIFY FAULT CURRENT. |