Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2003 | ELECTRIC - FINAL | Approved | ||
| 01/07/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*SENT TO TEP ON 1/16/03 AT 9:15AM. OK TO CLEAR. | |
| 12/17/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) VERIFY PERMIT FOR A/C 2.) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE A CLEAR AND LEVEL AREA. 2.) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE A CLEAR AND LEVEL AREA. 3.) PLEASE VERIFY 8' OF GROUND ROD IN SOIL ROD IS COT 4.) A PERMANENT METAL ADDRESS LABEL IS NEEDED. 5.) NO ENTRANCES OR EXIT FROM TOP WALL AS PER MANUFACTURES LABEL. 6.) A SEALING DEVICE ABOVE CURRENT CARRING PARTS AS PER MANFACTURES LABEL. 7.) WE HAVE MULTIPOLE TERMANATION AT GROUND LUG. 8.) PLEASE LABEL ALL BREAKERS. |