Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 12/24/02 AT 9:15AM OK TO CLEAR OK CABLE DROP. UNIT #1. | |
| 12/20/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1.) NO COMPLIANCE WITH NOTE #1 LAST INSP. 2.) RE LOCATE #4 GROUNDING ELECTRODE RUN THRU ATTIC TO OUTSIDE BLD. |
|
| 12/17/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) USE MIN 1/4" BOLTS TO ANCHOR RISER SUPPORT TO WALL, #8 DECK SCREW NOT SUFFICIANT. 2.) PLEASE PERMIT FOR WORK DONE ON #2 AND CALL IN FOR INSPECTION. 3.) NEED TO INSPECT WORK DONE OTHER SIDE OF FENCE, DOGS IN YARD, NO ANSWER AT DOOR. 4.) NEED TO VERIFY GROUND RODS, ADN GAS BONDING WIRING METHODE TO SUBPANELS 5.) LEAVE NAME & PH# OF LICENSED CONTR. DOING WORK. |
|
| 12/11/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0215*THE SERVICE PANELS WILL HAVE TO BE RELOCATED TO THE FRONT OF THE BUILDING BECAUSE THE CHAIN LINK FENCE ON THE PROPERLY LINE DOES NOT ALLOW THE REQUIRED NEC CLEARANCE. THE PANEL COVERS DO NOT OPEN FULLY DUE TO THE FENCE. SEE NEC 110-26. CORRECT AND RECALL. THANK YOU. |