Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* APPROVED OK TO CLEAR UPGRADE. |
|
| 01/03/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0910*PLEASE RESTRAIN DOGS. | |
| 01/02/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 12/30/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) BOND GAS PIPING. 2.) 60 AMP BREAKERS TO BIG FOR #8 WIRE, SHOULD BE 50A. BREAKER. 3.) USE MIN 1/4" BOLTS TO SUPPORT RISER CONDUIT. |