Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/31/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) A PERMANENT METAL ADDRESS LABEL IS NEEDED. 2.) PLEASE VERIFY GAS & WATER BONDS TO INTERIOR PIPE ALS WHERE ARE GROUND RODS. 3.) CONDUITS TO BE SUPPORTS WITHIN 3' OF BOX AS PER CODE 4.) BREAKER TO BE LABELED. 5.) ENTRANCES ABOVE CURRENT CARRING PARTS TO HAVE A WEATHER PROOF DEVICE. |