Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2002 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000*SENT TO TEP ON 12/13/02 AT 9:15AM CALL FOR FINAL INSPECTION WHEN YOU HAVE COMPLETED THE CUT OVER AND RECONNECTION OF THE POWER TO BOTH UNITS. 2.) REPLACE THE ADDRESS NUMBERS WITH METAL EMBOSSED DYMO STRIPS OR STICK ON NUMBERS. MAGIC MARKER.", PEN OR PENCIL ARE NOT ALLOWED ON EXTERIOR. THANKS MAC. |
|
| 12/10/2002 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection 0215* 1.) GROUND COLD WATER AND GAS LINES FROM 4509 TO PANEL GROUND. 2.) GROUND 4511 GAS LINE TO PANEL 3.) PLACE GROUND WIRE IN FRONT "POCKET" OF GROUND ROD CLAMPS. |