Permit: T02EL02311

Parcel: 11007383A


Addresses:

2519 N FAIR OAKS AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/04/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/28/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) GROUNDING TO HAVE PROPER TERMANATIONS. LUG HAS MULTIPOLE TERMANATIONS AND A LISTING FOR A SINGLE TERMINATION. ALSO SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING.
12/20/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) CONDUCTORS MUST BE SECURED TO 12 X 12 J-BOX TERMINATION. MUST BE PROTECTED IN RACEWAY. ALSO J-BOX TO BE SEALED PROPERLY TO PREVENT WATER FROM RUNNING BEHIND AND INTO STRUCTURE. 110-12 NEC ART 370 NEC.
2.) PVC EXPOSED ON WALL TO BE SCH 80 #9287 CITY ORDIN.
3.) CIRCUIT BREAKERS MUST BE I.D.