Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2003 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000* | |
| 03/06/2003 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection 0999*1.) PERMANENT METAL ADDRESS LABEL IS NEEDED. 2.) LABEL ALL BREAKERS. 3.) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE. 4.) FILL UNUSED OPENINGS IN PANEL. 5.) AN ANTI OXIDE COMPOUND IS NEEDED FOR ALUMINIUM CONDUCTORS. 7.) OLD PANEL WILL NOT BE ALLOWED TO BE USED AS A JUNCTION BOX. PLEASE PROVIDE AN APPROVED/LISTED BOX. |