Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) WE GROUNDED RECPTICALES ON UNGROUNDED SYSTEM. 2.) RECEPTICAL ABOVE COOLER TO BE WEATHERPROOF. 3.) UNIT HAS BEEN ADDED TO WITH NUMEROUS CIRCUITS SINCE ORIGINAL INSTALLATION. WE NOW HAVE MORE LOAD ON SERVICE THAN ORIGINAL INSTALLATION. SERVICE NEED TO BE UPGRADED TO HANDEL ADDITIONAL LOADS ADDED. |