Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE EQUIP. ENCLOSURES. PER 230 NEC & #9287 CITY ORDIN. 2.) SCH 40 PVC EXPOSED BELOW PANEL #1 TO BE INSTALLED IN SCH.80 #9287 CIYT ORDIN. 3.) PROVIDE LETTER FROM LICENSED CONTR. THAT EXAMINED ELECTRICAL WORK DONE, STATING UPON EXAMINATION OF EXISTING WORK DONE BY OWNER, IS SAFE AND IN GOOD OPERATING CONDITION. 4.) NO INCREASE IN REPLACED 60A DISC. SW WITH 125A SERVICE SIZE 8CKT. LOAD CENTER SUITABLE FOR USE AS SERVICE EQUIP. ANY? CALL791-5550 EXT 1136 BETWEEN 7-7:30 AM TALK TO RAY MAJUTA OR DAN SANTS CRUZ. |