Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/21/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 11/22/02 AT 9:15AM OK TO CLEAR TEMP SERVICE CALL FOR FINAL AFTER TIE IN FROM NEW SERVICE TO EXISTING. | |
| 11/19/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) SERVICE TOO HIGH SHOULD BE MAX 6' 7" TO HIGHEST BREAKER. 2.) BOND WATER & GAS 3.) RECALL FOR RE-INSP. WHEN DONE. ALSO SEE TEP SPECS. |