Permit: T02EL02253

Parcel: 122131570


Addresses:

1423 N BRYANT AV

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/27/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
1.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE.
2.) REQUIRE WATER AND GAS BOND.
3.) STRAP #4 GROUND TO WALL
4.) INSTALL AND SEAL ROOF JACK ON RISER AT SERVICE.
5.) PROVIDE NAME OF ELECTRICAL CONTRACTOR TO OFFICE LEAVE NAME AND LICENSE # GIVE TO PERMIT. COUNTER SO THEY CAN INCLUDE ON PERMIT. (MUST BE DONE PRIOR TO NEXT INSPECTION.