Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2002 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* | |
| 11/19/2002 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection 0000*BAY LIGHT ELECTRIC IS CONTRACTOR ON JOB. 1.) FINISH SEALING UNUSED OPENINGS AND STRAPING OF CONDUITS. |
|
| 11/18/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*1.) PLEASE HAVE A LICENSED L-11 ELECTRICAL CONTRACTOR SECURE/STRAP ALL LOOSE CONDUITS, FLEX CONDUITS, AND FILL UNUSED OPENING BOX, DISCONNECTS AND FIXTURES CLEAN UP EXPOSED CONDUCTORS THROUGH OUT ROOF. 2. ) WE HAVE CONDUIT LAYING ACCROSS ROOF THAT NEEDS SUPPORT ALSO BROKEN FITTINGS. ALSO DISCONNECT IN BROKEN CONDITION. |
|
| 11/14/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999* |