Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR. | |
| 11/14/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) SEALING DEVICES NEEDED ON ALL ENTRANCES ABOVE CURRENT PARTS. 2.) NEUTRAL OR GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH OF CONDUCTOR 200-7. 3.) CANNOT USE GREEN AS AN UNDERGOUNDED CONDUCTOR 210-5 250-134. |