Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TEP ON 4/3/03 AT 9:15AM OK TO CLEAR OK CABLE DROP. | |
| 04/01/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* | |
| 11/14/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) HOUSE ONLY HAS 1 20 AMP CIRCUIT ON A 50A 2 POLE BREAKER. IT IS INSUFFICIENT FOR A HOUSE THIS LARGE TO RUN ON ONE 20 AMP CIRCUIT. 2.) OPEN ROMEX BY STOVE CHASE OUT AND FINISH OR REMOVE. 3.) ALL DEVICE COVERS TO BE ON 4.) SMOKE DETECTORS REQUIRED IN BEDROOM 5.) MIDDLE BEDROOM CEILING NEED TO BE FINISHED. THE ELECTRICAL WIRING TO THIS HOUSE IS INSUFFICIENT OWNER NEEDS TO OBTAIN THE SERVICES OF A LICENSED ELECT CONTRACTOR TO WIRE HOUSE SAFELY, AND OBTAIN A PERMIT AND INSPECTIONS. |