Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2003 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* | |
| 01/22/2003 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0165* 1.) THE SMOKE DETECTORS ARE NOT INSTALLED. CURRENT CITY ORDINANCE REQUIRES A SMOKE DETECTOR IN EACH BEDROOM. THESE MAY BE BATTERY OPERATED. THEY MAY BE WALL OR CIELING MOUNTED. ONE IS REQUIRED IN HALL NEAR BEDRMS. A.) IF WALL MTD. THEY SHOULD BE NOT CLOSER THAN 6" NOR LOWER THAN 12" TO CIELING. B.) IF CIELING MOUNTED THEY MUST NOT BE CLOSER THAN 16" TO ANY WALL. C.) THEY SHOULD NOT BE CLOSER THAN 3FT. TO ANY AIR SUPPLY DUCT REGISTER. |
|
| 01/06/2003 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999* |