Permit: T02EL02203

Parcel: 134251520

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL02203

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 3/19/03 AT 9:15AM OK TO CLEAR OK CABLE DROP.
03/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0920*
NO ANSWER DOGS IN YARD.
11/13/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0215*
1.) PERMANENT ADDRESS LABEL REQUIRED BELOW METER. DO NOT USE "MAGIC MARKER" PEN, OR PENCIL
2.) YOU MUST INSTALL TWO (2) GROUND RODS. SET THEM 6' MINIMUM APART AND SINK THEM 2" BELOW GROUND LEVEL. LEAVE ENDS EXPOSED FOR INSPECTION. 3.) SET THE GROUND CLAMPS AHEAD OF THE PIPE UNIONS ON " HOUSE SIDE".
4.) INSTALL A SECOND PIPE CLAMP ON RISER PIPE WITHIN 8" OF THE PANEL. USE MINIMUM 1/4" LAG BOLTS.