Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 11/27/02 AT 9:15AM | |
| 11/19/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*PLEASE FINISH ITEMS # 1 & 7 OF PREVIOUS INSPECTION. | |
| 11/14/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) SUPPORT CONDUIT AS PER CODES. 2.) OUTLET COVERS TO BE WEATHERPROOF WHEN PLUGED IN 410-57. 3.) CORDS NOT TO BE HARD WIRED INTO BOXES UNLESS LISTED FOR USE. 4.) INSTALL ALL DEVICES INTO BOXES 5.) LIGHTING TO BE INSTALLED AS PER 6.) FILL UNUSED OPENINGS IN SUBPANEL. 7.) EXISTING SPRAY BOOTH HAS ELECTRICAL HAZARDS THAT NEED TO CORRECTED. 8.) MISSING JUNCTION BOX COVER & FACE PLATES. 9.) NEW OFFICE LIGHT FIXTURES TO BE GROUNDED AND USE AN APPROVED CONNECTOR. 10.) MECHANICAL UNIT ON ROOF AND SIGN NOT TO BE CORD CONNECTED PLEASE INSTALL AS PER CODED. A LICENSED L-11 ELECTRICAL CONTRACTOR TO PERFORM THIS WORK. |
|
| 11/13/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS. |