Permit: T02EL02174

Parcel: 137291470


Addresses:

1801 W OAK RIDGE CT

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
11/12/2002 ELECTRIC - RECONNECT Approved SENT TO TEP ON 11/13/02 AT 9:15AM OK TO CLEAR RECONNECT WILL NOTIFY TEP FOR CONNECTION.
11/06/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) IN SERVICE PANEL THE 40 AMP CIRCUIT BREAKER IS DAMAGED, THE CONDUCTOR CAN NO LONGER BE HELD IN THE TERMINAL DUE TO OVER HEATING CIRCUIT BREAKER TO BE REPLACED. CALL TUCSON ELECTRIC POWER REQUEST THAT THE TEP LOCK ON THE PANEL BE REMOVED SO THAT THE 40AMP CIRCUIT BREAKER WHICH IS IN THE PANEL CAN BE REPLACED THE RECAL FOR INSPECTION TO VERIFY THIS HAVE BEEN DONE AND POWER WILL BE RELEASED